SOP Guide for Pharma

API Manufacturing: SOP for Fire Extinguisher Inspection and Maintenance – V 2.0

API Manufacturing: SOP for Fire Extinguisher Inspection and Maintenance – V 2.0

Standard Operating Procedure for Fire Extinguisher Inspection and Maintenance in API Manufacturing

Department API Manufacturing
SOP No. SOP/API/204/2025
Supersedes SOP/API/204/2022
Page No. Page 1 of 13
Issue Date 14/04/2025
Effective Date 16/04/2025
Review Date 14/04/2026

1. Purpose

To establish a standardized procedure for monthly inspection, annual maintenance, refilling, tagging, and record-keeping of fire extinguishers installed in the API manufacturing facility. This ensures all firefighting equipment is in working condition and accessible during emergencies.

2. Scope

This SOP applies to all types of fire extinguishers located in the production, warehouse, utility areas, laboratories, corridors, and administrative

sections of the API manufacturing site. It includes CO₂, ABC, DCP, Foam, and Water-type extinguishers.

3. Responsibilities

  • Engineering/Maintenance Team: Conduct monthly inspections and ensure refilling and pressure checks are completed.
  • EHS Officer: Maintain fire extinguisher inventory and coordinate third-party annual maintenance.
  • QA Team: Audit compliance with fire safety SOPs and review inspection records.

4. Accountability

The Head of Engineering and Head of EHS are jointly accountable for ensuring that fire extinguishers are always maintained in a functional state and in compliance with fire safety regulations and internal policies.

5. Procedure

5.1 Fire Extinguisher Identification and Placement

  1. Each fire extinguisher shall be assigned a unique identification number (e.g., FE-API-001).
  2. Ensure extinguishers are:
    • Mounted at an accessible height (not exceeding 1.5 meters)
    • Free from obstructions
    • Located near potential fire hazards (machinery, solvent areas)
  3. Update the Fire Extinguisher Location Map (Annexure-1) after any relocation.

5.2 Monthly Visual Inspection

  1. Conducted by the Maintenance or EHS team using the Monthly Inspection Checklist (Annexure-2).
  2. Check the following parameters:
    • Pressure gauge (in green zone)
    • Nozzle and safety pin intact
    • External body free from corrosion or damage
    • Clear label and operating instructions
    • Inspection tag present and signed
  3. Tag the extinguisher after inspection with the month/year and inspector’s initials.

5.3 Annual Maintenance and Servicing

  1. Engage an authorized fire safety vendor to:
    • Open, refill, or recharge extinguishers as applicable
    • Replace faulty valves, pipes, and O-rings
    • Check weight of CO₂ extinguishers
  2. Vendor must provide a Fire Extinguisher Servicing Report (Annexure-3).

5.4 Recharging and Replacement Criteria

  1. Extinguishers must be recharged or replaced if:
    • Pressure is below recommended level
    • Seal or pin is broken
    • Used even partially during an incident
    • Expired per manufacturer’s instructions
  2. Dispose of expired or damaged extinguishers via authorized scrap vendor as per SOP/API/203/2025.

5.5 Record Keeping

  1. Maintain the Fire Extinguisher Master Register (Annexure-4) with the following:
    • Extinguisher ID
    • Type and capacity
    • Location
    • Inspection and servicing history
  2. Inspection reports must be signed and archived for a minimum of 5 years.

5.6 Mock Drill Coordination

  1. QA and EHS must ensure use of one extinguisher during quarterly mock fire drills for training purposes.
  2. Replace the used unit immediately and update the logbook accordingly.

5.7 Tagging Protocol

  1. Use color-coded inspection tags (green, yellow, red) to indicate:
    • Green – Recently inspected and in good condition
    • Yellow – Due for refilling
    • Red – Out of order
  2. Tag details must match the Fire Extinguisher Tag Format (Annexure-5).

6. Abbreviations

  • EHS: Environment, Health & Safety
  • CO₂: Carbon Dioxide
  • ABC: Multipurpose Dry Chemical
  • DCP: Dry Chemical Powder
  • SOP: Standard Operating Procedure

7. Documents

  1. Fire Extinguisher Location Map – Annexure-1
  2. Monthly Inspection Checklist – Annexure-2
  3. Fire Extinguisher Servicing Report – Annexure-3
  4. Fire Extinguisher Master Register – Annexure-4
  5. Fire Extinguisher Tag Format – Annexure-5

8. References

  • National Building Code of India – Part 4 (Fire and Life Safety)
  • NFPA 10 – Standard for Portable Fire Extinguishers
  • Factory Act, 1948 – Safety Provisions
  • Fire Services Department Guidelines (State-specific)

9. SOP Version

Version: 2.0

10. Approval Section

Prepared By Checked By Approved By
Signature
Date
Name
Designation
Department

11. Annexures

Annexure-1: Fire Extinguisher Location Map

A floor-wise site map indicating each fire extinguisher ID and type with assembly point markings.

Annexure-2: Monthly Inspection Checklist

Extinguisher ID Type Pressure Seal Intact Tag Updated Remarks
FE-API-001 CO₂ OK Yes Apr-25

Annexure-3: Fire Extinguisher Servicing Report

ID Type Service Date Vendor Next Due
FE-API-003 ABC 10/04/2025 FireSecure Ltd. 10/04/2026

Annexure-4: Fire Extinguisher Master Register

ID Location Type Capacity Install Date Last Inspection
FE-API-005 Warehouse Entry Foam 9 L 01/06/2023 01/04/2025

Annexure-5: Fire Extinguisher Tag Format

Month Year Inspected By Remarks
April 2025 Rajesh Kumar OK

Revision History:

Revision Date Revision No. Details Reason Approved By
01/01/2022 1.0 Initial Issue New SOP QA Head
14/04/2025 2.0 Annexure additions and tagging protocol Compliance Enhancement QA Head