Standard Operating Procedure for Fire Extinguisher Inspection and Maintenance in API Manufacturing
| Department | API Manufacturing |
|---|---|
| SOP No. | SOP/API/204/2025 |
| Supersedes | SOP/API/204/2022 |
| Page No. | Page 1 of 13 |
| Issue Date | 14/04/2025 |
| Effective Date | 16/04/2025 |
| Review Date | 14/04/2026 |
1. Purpose
To establish a standardized procedure for monthly inspection, annual maintenance, refilling, tagging, and record-keeping of fire extinguishers installed in the API manufacturing facility. This ensures all firefighting equipment is in working condition and accessible during emergencies.
2. Scope
This SOP applies to all types of fire extinguishers located in the production, warehouse, utility areas, laboratories, corridors, and administrative
3. Responsibilities
- Engineering/Maintenance Team: Conduct monthly inspections and ensure refilling and pressure checks are completed.
- EHS Officer: Maintain fire extinguisher inventory and coordinate third-party annual maintenance.
- QA Team: Audit compliance with fire safety SOPs and review inspection records.
4. Accountability
The Head of Engineering and Head of EHS are jointly accountable for ensuring that fire extinguishers are always maintained in a functional state and in compliance with fire safety regulations and internal policies.
5. Procedure
5.1 Fire Extinguisher Identification and Placement
- Each fire extinguisher shall be assigned a unique identification number (e.g., FE-API-001).
- Ensure extinguishers are:
- Mounted at an accessible height (not exceeding 1.5 meters)
- Free from obstructions
- Located near potential fire hazards (machinery, solvent areas)
- Update the Fire Extinguisher Location Map (Annexure-1) after any relocation.
5.2 Monthly Visual Inspection
- Conducted by the Maintenance or EHS team using the Monthly Inspection Checklist (Annexure-2).
- Check the following parameters:
- Pressure gauge (in green zone)
- Nozzle and safety pin intact
- External body free from corrosion or damage
- Clear label and operating instructions
- Inspection tag present and signed
- Tag the extinguisher after inspection with the month/year and inspector’s initials.
5.3 Annual Maintenance and Servicing
- Engage an authorized fire safety vendor to:
- Open, refill, or recharge extinguishers as applicable
- Replace faulty valves, pipes, and O-rings
- Check weight of CO₂ extinguishers
- Vendor must provide a Fire Extinguisher Servicing Report (Annexure-3).
5.4 Recharging and Replacement Criteria
- Extinguishers must be recharged or replaced if:
- Pressure is below recommended level
- Seal or pin is broken
- Used even partially during an incident
- Expired per manufacturer’s instructions
- Dispose of expired or damaged extinguishers via authorized scrap vendor as per SOP/API/203/2025.
5.5 Record Keeping
- Maintain the Fire Extinguisher Master Register (Annexure-4) with the following:
- Extinguisher ID
- Type and capacity
- Location
- Inspection and servicing history
- Inspection reports must be signed and archived for a minimum of 5 years.
5.6 Mock Drill Coordination
- QA and EHS must ensure use of one extinguisher during quarterly mock fire drills for training purposes.
- Replace the used unit immediately and update the logbook accordingly.
5.7 Tagging Protocol
- Use color-coded inspection tags (green, yellow, red) to indicate:
- Green – Recently inspected and in good condition
- Yellow – Due for refilling
- Red – Out of order
- Tag details must match the Fire Extinguisher Tag Format (Annexure-5).
6. Abbreviations
- EHS: Environment, Health & Safety
- CO₂: Carbon Dioxide
- ABC: Multipurpose Dry Chemical
- DCP: Dry Chemical Powder
- SOP: Standard Operating Procedure
7. Documents
- Fire Extinguisher Location Map – Annexure-1
- Monthly Inspection Checklist – Annexure-2
- Fire Extinguisher Servicing Report – Annexure-3
- Fire Extinguisher Master Register – Annexure-4
- Fire Extinguisher Tag Format – Annexure-5
8. References
- National Building Code of India – Part 4 (Fire and Life Safety)
- NFPA 10 – Standard for Portable Fire Extinguishers
- Factory Act, 1948 – Safety Provisions
- Fire Services Department Guidelines (State-specific)
9. SOP Version
Version: 2.0
10. Approval Section
| Prepared By | Checked By | Approved By | |
|---|---|---|---|
| Signature | |||
| Date | |||
| Name | |||
| Designation | |||
| Department |
11. Annexures
Annexure-1: Fire Extinguisher Location Map
A floor-wise site map indicating each fire extinguisher ID and type with assembly point markings.
Annexure-2: Monthly Inspection Checklist
| Extinguisher ID | Type | Pressure | Seal Intact | Tag Updated | Remarks |
|---|---|---|---|---|---|
| FE-API-001 | CO₂ | OK | Yes | Apr-25 | — |
Annexure-3: Fire Extinguisher Servicing Report
| ID | Type | Service Date | Vendor | Next Due |
|---|---|---|---|---|
| FE-API-003 | ABC | 10/04/2025 | FireSecure Ltd. | 10/04/2026 |
Annexure-4: Fire Extinguisher Master Register
| ID | Location | Type | Capacity | Install Date | Last Inspection |
|---|---|---|---|---|---|
| FE-API-005 | Warehouse Entry | Foam | 9 L | 01/06/2023 | 01/04/2025 |
Annexure-5: Fire Extinguisher Tag Format
| Month | Year | Inspected By | Remarks |
|---|---|---|---|
| April | 2025 | Rajesh Kumar | OK |
Revision History:
| Revision Date | Revision No. | Details | Reason | Approved By |
|---|---|---|---|---|
| 01/01/2022 | 1.0 | Initial Issue | New SOP | QA Head |
| 14/04/2025 | 2.0 | Annexure additions and tagging protocol | Compliance Enhancement | QA Head |